PCS 1200kW

By controlling the charging and discharging process of the battery, the 1200kW PCS can conduct AC/DC conversion and directly supply power to AC loads without power grid. PCS is composed of DC/AC bidirectional converter, control unit, etc. The PCS controller receives background control commands through communication, controls the converter to charge or discharge the battery according to the symbol and size of the power command, and realizes the regulation of the active power and reactive power of the grid. The PCS controller communicates with the BMS through the CAN interface to obtain the status information of the battery pack, which can realize the protective charging and discharging of the battery and ensure the safe operation of the battery.

SN

Item

Parameters

Notes

AC Measurement Parameters

1

AC Access Method

Three Phases and Three Lines


2

Rated Power 

1200kw


3

Overload Capability

110%:Long-term Operation

40ºC has 1.1 Times Continuous Overload and 45ºC Full Load.

120%: No Less than 2min

30~35ºC  can respond for 10 minutes, and more than 40ºC  can only meet 2 minutes.

4

AC Side Rated Voltage

480V

It can adapt to the fluctuation of ±10% intervoltage.

5

Rated Grid Frequency

50HZ/60HZ

It is consistent with the frequency of the power grid.

6

Total Current Waveform Distortion Rate(THD)

<3%(Rated power )

The distortion rate of total current waveform at rated power<3%

7

Power Factors

>0.9(leading or lagging)


8

Power Controldeviation Time

≤30ms


9

Power Controldeviation

2%

When the power is greater than 20% of the rated power, the power control deviation does not exceed 2%.

10

Direct Current Component

0.5%(Rated current)

The rated power operation is that the DC current component on the AC side does not exceed 0.5% of the rated current.

DC Measurement Parameters

1

DC Voltage Range

679~1500v


2

Full Power DC Voltage Range

679~1500v


3

Voltage Regulator Accuracy

±2%


4

Flow Stabilization Accuracy

±2%


Protect

1

Low-voltage Crossing

HAVE


2

High Voltage Crossing

HAVE


3

Protection Against Isolated Islands

HAVE


4

AC Overcurrent/Short Circuit Protection

HAVE


5

AC overvoltage/ undervoltage protection

HAVE


6

AC Overfrequency/Unfrequency Protection

HAVE


7

AC Incoming Phase Sequence Error Protection

HAVE